Note: The iMaster controller is compatible with various (4–20 mA) sensors that customers may recommend for use.
Ghi chú: Bộ kiểm soát iMaster phù hợp với nhiều đầu dò (4 - 20 mA) khác nhau mà khách hàng có thể giới thiệu để sử dụng
| No | Product Code | Range | K |
De. Limit |
RS 485 |
420 mA |
Res. |
Acc. |
Max Press. |
Max Temp. |
Voltage (V) |
IP |
Body Material |
Connection | ||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| PSI | Bar | °F | °C | |||||||||||||
| Notes: De.= Detection; Res.= Resolution; Acc.= Accuracy; Temp.= Temperature; Press.= Pressure; IP= Ingress Protection | ||||||||||||||||
| 1A | Conductivity sensor (many applications) | |||||||||||||||
| 1 | Cond20-4-60 Cond200-4-60 Cond2K4-60 |
0 - 20 μS/cm 0 - 200 μS/cm 0 - 2,000 μS/cm |
0.01 0.1 1.0 |
0.05 0.1 10.0 |
✔ | ✔ | 0.01 0.1 1.0 |
±2%FS | 56 | 4 | 140 | 60 | 12-24 | IP68 | SS 316 | G3/4; NPT3/4 |
| 2 | Cond20-6-130 Cond200-6-130 Cond2K-6-130 |
0 - 20 μS/cm 0 - 200 μS/cm 0 - 2,000 μS/cm |
0.01 0.1 1.0 |
0.05 0.1 |
✔ | ✔ | 0.01 0.1 1.0 |
±2%FS | 84 | 6 | 266 | 130 | 12-24 | IP65 | 316L Titanium Alloy and Platinum | NPT3/4 |
| 3 | Cond20K-4-60 Cond200K-4-60 |
0 - 20 mS/cm 0 - 200 mS/cm |
1 | 1 | ✔ | ✔ | 1 | ±2%FS | 56 | 4 | 140 | 60 | 12-24 | IP68 | PPS; ABS | G3/4; NPT3/4 |
| 4 | Cond20K-4-60 Cond200K-4-60 |
0 - 20 mS/cm 0 - 200 mS/cm |
10 | 0.01 | ✔ | ✔ | 0.1 | ±2%FS | 56 | 4 | 140 | 60 | 12-24 | IP68 | SS316 | G3/4; NPT3/4 |
| 5 | Pyxis ST-723 (Cond20K-21-200) |
0 - 20,000 μS/cm | 0.3 | 1 | ✔ | ✔ | 0.1 | ±3.5%FS | 290 | 20.6 | 392 | 200 | 24 | IP67 | SS316 | NPT3/4 |
| 1B | Inductive conductivity (Electrodeless / Toroidal) sensor ( used in water industry and production) | |||||||||||||||
| 1 | ICond200K-16-100 | 0-200mS/cm | 1 | 0.1 | ✔ | ✔ | 0.1 | ±0.5%FS | 225 | 16 | 212 | 100 | 12-24 | IP65 | PP,PFA | NPT3/4; 1/2 |
| 2 | PH sensor(many applications) | |||||||||||||||
| 1 | pH014-2-50 | 0 - 14 | ✔ | ✔ | 0.01 | ±0.02 | 28 | 2 | 140 | 60 | 12-24 | IP68 | PPS; ABS; SS316 | G3/4; NPT3/4 | ||
| 2 | Pyxis ST-710SS | 0 - 14 | ✔ | ✔ | 0.01 | ±0.01 | 98 | 7 | 39-120 | 4-49 | 12-36 | IP67 | 316 SS | NPT3/4 | ||
| 3 | pH014-6-130 | 0 - 14 | ✔ | ✔ | 0.1 | ±0.05 | 84 | 6 | 266 | 130 | 12-24 | IP65 | Glass | PG13.5 &VP/K8S/S8 | ||
| 4 | pH014-3-90 | 0 - 14 | ✔ | ✔ | 0.01 | ±0.05 | 42 | 3 | 194 | 90 | 12-24 | IP65 | PPS | 3/4NPT | ||
| 3 | ORP sensor (cooling, clean; RO and pool water; disinfection…) | |||||||||||||||
| 1 | ORP1500-2-60 | -1,500…+1,500 mV | ✔ | ✔ | 1 | ±15%FS | 28 | 2 | 140 | 60 | 12-24 | IP68 | PPS; SS316; ABS | G3/4; NPT3/4 | ||
| 2 | Pyxis ST-711SS | -1,500…+1,500 mV | ✔ | ✔ | 1 | ±1%FS | 98 | 7 | 40-120 | 4-49 | 12-36 | IP67 | 316 SS | NPT3/4 | ||
| 4 | Corrosion sensor (Cooling, chiller and other water system). Replaceable wetted metal materials: copper, carbon steel, stainless steel, or aluminum… | |||||||||||||||
| 1 | CR3-60C/CS/SS/Al | 0.001-995 MPY 0 - 5.000 mm/a |
0.004 | ✔ | ✔ | 0.001 | ±3%FS | 42 | 3 | 140 | 60 | 12-24 | IP68 | SS304 | M39x1.5; G1 | |
| 2 | Pyxis CR-300 | 0.001-995 MPY 0 - 5.000 mm/a |
0.001 | ✔ | ✔ | 0.001 | - | 98 | 7 | 14-122 | -10-50 | 24 | IP65 | SS304 | NPT 1 | |
| 3 | Pyxis CR-301 | 0.001-995 MPY 0 - 5.000 mm/a |
0.001 | ✔ | ✔ | 0.001 | - | 500 | 34 | 14-464 | -10-240 | 24 | IP68 | Titanium + PEEK | NPT 3/4 | |
| 5 | PTSA sensor (Cooling, chiller, RO sytem and Leak detection) | |||||||||||||||
| 1 | PTSA200-3-60M PTSA1K-3-60M |
0 - 200 ppb 0 - 1,000 ppb |
✔ | ✔ | 0.1 | ±0.25 ppb | 42 | 3 | 140 | 60 | 12-24 | IP68 | SS316 | G3/4 | ||
| 2 | Pyxis ST-500 | 0 - 200 ppb | - | ✔ | ✔ | ±1 | ±1 ppb | 98 | 7 | 120 | 49 | 22-26 | IP67 | CPVC | NPT3/4 | |
| 6 | Tagged sensor (cooling, chiller, RO system) | |||||||||||||||
| 1 | Pyxis ST-590 | 0 - 20 ppm | - | ✔ | ✔ | ±1 | ±0.1 ppm | 98 | 7 | 120 | 49 | 22-26 | IP67 | Quartz & UPVC | NPT3/4 | |
| 7 | Fluorescent (Low pressure boiler and hot water) | |||||||||||||||
| 1 | Pyxis ST-525 /525SS | 0 - 60 ppb | ✔ | ✔ | ±0.2ppb | - | 98/281 | 7/20 | 120 | 49 | 22-26 | IP67 | uPVC /SS304 | NPT3/4 | ||
| 2 | Pyxis ST-525-HR /525SS-HR | 0 - 500 ppb | ✔ | ✔ | ±0.2ppb | - | 98/281 | 7/20 | 120 | 49 | 22-26 | IP67 | uPVC /SS304 | NPT3/4 | ||
| 8 | Turbidity (many applications) | |||||||||||||||
| 1 | TUR20-1-60 TUR4K-2-60 TUR4K-3-60 |
1…20 NTU 1...4,000 NTU 1...4,000 NTU |
0.01 1 0.1 |
✔ | ✔ | 0.1 10 1 |
±2%FS ±5%FS ±5%FS |
14 28 42 |
1 2 3 |
113 | 45 | 12 | IP68 | ABS POM SS316 |
M12 connector G3/4 G3/4,G1 |
|
| 2 | Pyxis ST-730B | 0-1,000NTU | 1 | ✔ | ✔ | 1 | ±2%FS | 98 | 7 | 122 | 50 | 22-26 | IP66 | uPVC | NPT3/4 | |
| 9 | DO sensor (Boiler feed water, chiller water; bio-waste water, aquaculture…) | |||||||||||||||
| 1 | DO20-2-60 (Low temp) | 0.01 - 20.00 mg/l | 0.01 | ✔ | ✔ | 0.01 | ±2%FS | 28 | 2 | 140 | 60 | 12-24 | IP68 | POM+316SS; ABS | G3/4,G1; M39*1.5 | |
| 2 | DO20-2-120 (High temp) | 0.01 - 20.00 mg/l | ✔ | 0.01 | ±2%FS | 28 | 2 | 248 | 120 | 12-24 | IP68 | SS 316 | PG13.5 | |||
| 3 | DO20-3-100 (High temp) | 0.01 - 20.00ug/l(ppb) | ✔ | 10 | ±2%FS | 42 | 3 | 212 | 100 | 12-24 | IP68 | SS 316 | PG13.5 | |||
| 4 | Pyxis ST-774 | 0.4–2,000 ug/l(ppb) (0 - 2 mg/l) |
0.1 | ✔ | ✔ | 0.1µg/L | ±0.3µg/l | 141 | 10 | 122 | 50 | IP67/68 | SS 316 | ¼ inch OD | ||
| 10 | Free chlorine, Cl2 (cooling, clean and pool water; disinfection…) | |||||||||||||||
| 1 | FCL20-1-50 | 0…20 mg/l | ✔ | ✔ | 0.01 | ±2% | 14 | 1 | 140 | 60 | 12-24 | IP68 | POM + 316SS; ABS | M39*1.5 | ||
| 2 | Pyxis ST-765SS-FCL/CLO | 0.00-5.00ppm | ✔ | ✔ | ±0.01mg/L | ±1%FS | 98 | 7 | 104 | 40 | 22-26 | IP67 | uPVC | ¼ inch OD | ||
| 11 | Chloride, Cl- (Cooling - chiller, soft, boiler, RO water; brackish…) | |||||||||||||||
| 1 | CL35K1-50 | 2 - 35,000 mg/l Cl- | 1.8 | ✔ | ✔ | 0.01mg/l | ±5%FS | 14 | 1 | 122 | 50 | 12-24 | IP68 | PPS; 316SS; ABS | G3/4; NPT3/4 | |
| 12 | Calcium hardness (Cooling, chiller water…) | |||||||||||||||
| 1 | Ca6K1-50 | 0.1..6,400 mg/lCa2+ | 0.1 | ✔ | ✔ | 0.1mg/l | ±5%FS | 14 | 1 | 122 | 50 | 12-24 | IP68 | PPS; 316SS; ABS | G3/4; NPT3/4 | |
| 13 | Total hardness (cooling, chiller, RO, boiler, soft, clean water…) | |||||||||||||||
| 1 | TH1K1-40 | 0..1,000 mg/lCaCO3 | ✔ | ✔ | 0.1mg/l | ±10%FS | 14 | 1 | 104 | 40 | IP68 | SS316L | NPT3/4 | |||
| 14 | TSS (Cooling -chiller, clean & waste water...) | |||||||||||||||
| 1 | TSS10K3-60M TSS30K3-60M |
1 - 10,000 mg/l 1 - 30,000 mg/l |
1 10 |
✔ | ✔ | 0.01 | ±5%FS | 42 | 3 | 32-140 | 0-60 | 12-24 | IP68 | SS316 | NPT3/4 | |
| 2 | Pyxis LT-635 | 0.00 - 30,000mg/L | 0.01 | ✔ | ✔ | 0.01 | ±5% | 42 | 3 | 32-122 | 0-50 | 22-26 | IP68 | SS316 | MNPT3/4 | |
| 15 | Level sensor( water, chemical level) | |||||||||||||||
| 1 | LS10 Ultrasonic Level Sensor |
0.5 - 10 m | 0.5 | ✔ | ✔ | 1mm | ±0.2% | - | - | -4-122 | -20-50 | 12-24 | IP68 | ABS | M60x2 | |
| 2 | Pyxis LS-200 Ultrasonic Level Sensor |
0.1 - 2.7 m | 0.1 | ✔ | ✔ | 0.5mm | ±0.15% FS | 28 | 2 | 14-122 | -10-50 | 24 | IP67 | PVDF | MNPT 1 | |
| 3 | Pyxis LSR-801 Radar Level Sensor |
0.05–15m | 0.1 | ✔ | ✔ | (0.5mm) | ±2% FS | 56 | 4 | 59-122 | -15-50 | 24 | IP67 | PBT | MNPT 2 | |
| 16 | Ozone sensor ( Drinking water, clean water, disinfection…) | |||||||||||||||
| 1 | OZ-20-2-6 | 0.00 - 20,000 mg/l | 0.01 | ✔ | ✔ | 0.01 | 0.01 | 28 | 2 | 32-140 | 0-60 | 12-24 | IP68 | POM | G3/4; NPT3/4 | |
| 17 |
Other probes for wastewater (e.g., NO₃⁻, NH₄⁺, BOD, COD, heavy metals), potable water, environmental monitoring; flow and level/solids measurement; and flue gas are all available and integrated with the iMaster controller. |
|||||||||||||||
| ABS = Acrylonitrile Butadiene Styrene; PP = Polypropylene; POM = Polyoxymethylen; SS = Stainless Stee; CPVC = Chlorinated PVC; PC = Polycarbonate; PBT = Polybutylene Terephthalate; PVDF = Polyvinylidene fluoride; uPVC = unplasticized polyvinyl chloride | ||||||||||||||||
Have questions? Our team's here to help.